Rz089status Version 2.0

Start: 2023-06-21 06:34:20
Department: Rechenzentrum
Priority: Normal
End: 2023-06-21 17:01:55
Affected: Alle Kunden
Typ: Störung
DateTime Description Lang
2023-06-21 04:35:36 We are investigating a level 3 power outage for certain customers eng
2023-06-21 04:35:36 Wir prüfen einen Stromausfall im Level3 für bestimmte Kunden. ger
2023-06-21 04:49:59 A power failure affects users of 5$ racks series connected to PDU3 or PDU4. We opened a case ticket with Lumen. eng
2023-06-21 04:49:59 See DE ger
2023-06-21 04:58:08 The power outage only affects the a-feed, not the b-feed. eng
2023-06-21 04:58:08 See DE ger
2023-06-21 05:56:30 PDU3 is broken. eng
2023-06-21 05:56:30 See ENG ger
2023-06-21 08:23:28 The main fuse for our sub-distribution of the racks on PDU3 is defective and must be measured and replaced if necessary. This process has started, next update in ~4h. eng
2023-06-21 08:23:28 Hauptsicherung für unsere Unterverteilung der Racks an PDU3 ist defekt und muss gemessen und ggf. getauscht werden. Dieses Prozess ist angestossen, naechstes Update in ~4h. ger
2023-06-21 14:02:36 The repair work has been started. eng
2023-06-21 14:02:36 See DE ger
2023-06-21 15:14:43 Repair work is done. Unfortunately, we triggered another cabinet fuse in the course of the work, which led to the failure of one rack. Further planned maintenance work is necessary here because a rack PDU was defective here. eng
2023-06-21 15:14:43 Reparaturarbeiten sind erledigt. Leider haben wir im Zuge der Arbeiten eine andere Cabinetsicherung ausgeloest, dies fuehrte zum Ausfall für ein Rack. Hier sind weitere geplante Wartungsarbeiten notwendig, da hier eine Rack-PDU defekt wurde. Diese werden noch angekuendigt. ger